MPO/MTP Adapter

Article Number: 228072

Fast and accurate MPO/MTP® cabling and component testing with WireXpert certifier

This MPO test solution enables data center IT-managers, -technichians and -installers to get quick and accurate assessment of the quality of MPO cabling.
Additionally, it helps in performing incoming inspection of MPO components as i.e. trunk cables, fan-out cables and cassettes.
The key feature of this solution is a 5-second Autotest that includes the detection of fiber connection map and the measurement of loss on each fiber.

  • MPO/MTP testing with WireXpert WX4500-FA cable certifier
  • MPO Autotest in less than 5 seconds
  • Reporting is integrated in eXport software together with standard single fiber and copper test results
  • Testing MPO-to-SC/LC links for end-to-end loss measurement on individual fibers
  • Testing connectivity from MPO to individual fibers
  • Allows configuring number of active fibers in MPO, making it possible to test i.e. custom links, including 8-fiber links
  • Automatically identifies connection type as type A, B, C or customized
  • Allows reference settings with any connection type
  • Displays absolute power level and loss on each fiber

Highlights

  • A cable certifier for testing copper, fiber, and MPO cabling runs
  • Easy troubleshooting of connection problems
  • Higher productivity through a complete, accurate and versatile test system

Technical Details

General specifications

Autotest

5 seconds

Test parameters

Loss per channel in graphical and tabular format type of link (A,B,C, or custom),
PASS/FAIL against standard / user set limit

MPO link configurations

All 12 fibers or user selected fibers

Test Configurations

MPO-MPO
MPO-SC/LC (requires multimode fiber adapter WX_AD_MM on local unit)

MPO Source adapter

Fiber/connector type

Multimode MPO (type A, pinned)

Wavelength

830nm - 860nm

Measurement requirements

The measurements are taken using a 50µm multimode fibers in accordance with the TIA/EIA-455-203 (FOTP-203) standard test requirement.

MPO Power Meter adapter

MPO Power Meter adapter

Fiber/connector type multimode MPO (Type A pinned)

Input optical power level at saturation

-1.0dBm

Loss measurement dynamic range

0-15 dB

Loss measurement accuracy

+- 0.2dB

Delivery

  • WX_AD_MM_MPO_KIT
  • Light Source & Power Meter
  • 2x Typ A test cablel "unpinned to pinned"
  • 2x Typ A adapter
  • Typ A reference cable "unpinned to unpinned"
  • Typ B reference cable "unpinned to unpinned"
  • MPO Cleaning Kit

Documents

Videos

MPO Testing with WireXpert 4500

FAQ

With the WireXpert and fiber adapters you can perform a fully standards-compliant certification measurement Tier 1 (e.g. according to ISO / IEC 14763-3). Additionally, an automated evaluation of the attenuation of the fiber link is performed in terms of the number of the connectors, splices, and the length of the link.
(Automated evaluation of the link attenuation budget)

Yes, for standard-compliant measurements on fiber optic cabling (e.g. according to ISO / IEC 14763-3) you must be equipped with a fiber microscope and cleaning tools, as it is normative required to review the connector end faces for dirtiness. You would also know nothing about the dirtiness of the connectors and could unintentionally cause pollution to the fiber cabling.